Delta DVP-ES2 — 3.8 Detailed Instruction Explanation

3. Instruction Set API 59 Operands: S 1 : Maximum frequency (Hz) S 2 : Number of pulses S 3 : Ramp up/down time (ms) D : Pulse output device (Y0, Y1, Y2 and Y3 are available) (DVP-12SE does not support Y1 and Y3.) Explanations: 1. PLSR instruction performs a frequency ramp up/down process when positioning. Speed ramp up process is activated between static status to the target speed. Pulse output persists in target speed before getting close to target position. When target position is near, speed ramp down process executes, and pulse output stops when target position is achieved. 2. Set range of S 1 pulse output frequency: 3.

When output device is specified with Y0, Y2, the start/end frequency of Y0 is set by D1340 and start/end frequency of Y2 is set by D1352. 4. When output device is specified with Y1, Y3, the start/end frequency is 0Hz. 5. When D1220/D1221 = K1 or K2, positive/negative sign of S2 denotes pulse output direction. 6. PLSR instruction supports two modes of pulse output as below list. 7. When assigning Y0 and Y2 output mode as Pulse, i.e. D1220 = K0, D1221 = K0, the available range for S 2 is 1~32,767 (16-bit instruction) and 1~2,147,483,647 (32-bit instruction).

3-147 Mnemonic Operands Function Controllers D PLSR Pulse Ramp ES2/EX2 SS2 SA2 SX2 SE Type OP Bit Devices Word devices Program Steps X Y M S K H KnX KnY KnM KnS T C D E F PLSR: 9 steps DPLSR: 17 steps S 1 * * * * * * * * * * * S 2 * * * * * * * * * * * S 3 * * * * * * * * * * * D * 16-bit 32-bit SS SA2 2 SE SX2 SA2 SA2 ES2/EX2 SS2 SX2 ES2/EX2 SS2 SX2 SE SE Range of S 1 pulse output frequency: Output frequency: Output Y0, Y2 Y1, Y3 16-bit SS2: 6~10,000Hz ES2/EX2/SA2/SX2/SE: 6~32,767Hz 6~10,000Hz 32-bit SS2: 6~10,000Hz ES2/EX2/SA2/SX2/SE: 0~100,000Hz 6~10,000Hz If frequency smaller than 6Hz is specified, PLC will output 6Hz.

If frequency bigger than max frequency is specified, PLC will output with max frequency. Mode D1220 D1221 Output K0 K1 K0 K1 Y0 Pulse Pulse Y1 Pulse Dir Y2 Pulse Pulse Y3 Pulse Dir