Delta DVP-ES2 — 3.8 Detailed Instruction Explanation

DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming 8. When assigning Y0 and Y2 output mode as Pulse/Dir, i.e. D1220 = K1, D1221 = K1, the available range for S 2 is 1~32,767 or -1~-32,768 (16-bit instruction) and 1~2,147,483,647 or -1~-2,147,483,648 (32-bit instruction) and 1~2,147,483,647 (32-bit instruction). 9. When assigning output device as Y1 and Y3, the available range for S 2 is 1~32,767 (16-bit instruction) 10. S 3 : Ramp up/down time (unit: ms, min. 20ms). When assigning output device as Y1 and Y3, the set value of ramp up and ramp down time should be the same. When assigning output device as Y0 and Y2, and if:

 M1534 = OFF (Y0) and M1535 = OFF (Y2), the ramp up and ramp down time should be the same.  M1534 = ON and M1535 = ON, then S 3 specifies ramp up time only. The ramp down time is specified by value set in D1348 (Y0) and D1349 (Y2). 11. When M1257 = OFF, ramp up/down curve of Y0 and Y2 is straight line. When M1257 = ON, ramp 12. The output will not be affected if S 1 , S 2 or S 3 are changed when PLSR instruction is being executed. up/down curve will be S curve. The ramp up/down curve of Y1 and Y3 is fixed as straight line PLSR instruction has to be stopped if changing values in S 1 , S 2 or S 3 is required. 13. Flags for indicating pulse output status:

a) When pulse output on Y0/Y1 specified as Pulse/Dir (D1220 = K1) is completed, completion flag M1029 = ON. b) When pulse output on Y2/Y3 specified as Pulse/Dir (D1221 = K1) is completed, completion flag M1102 = On 。 14. During the ramp up process, the pulse numbers (frequency x time) of each speed shift may not all be c) When PLSR/DPLSR instruction is activated again, the completion flags will automatically be reset. integer values, but PLC will operate integer value only. In this case, the omitted decimals will result in errors between each speed shift, i.e. pulse number for each shift may differ due to this operation.

For ensuring the required output pulse number, PLC will fill in pulses as need automatically in order to correct the deviation. 15. There is no limitation on the times of using this instruction in the program. However, only 4 instructions can be executed at the same scan time. When several pulse output instructions (PLSY, PWM, PLSR) use Y1 as the output device in the same scan cycle, PLC will execute pulse output according to the driven order of these instructions. 16. Set value falls out of the available range of operands will be automatically corrected with the min. or max available value. 17.

When M1334 or M1335 is enabled, execute API59 PLSR/DPLSR instructions on Y0 or Y2 to ramp-down when the conditional contacts are closed. 3-148 Output Y0 Y1 Y2 Y3 Completion M1029 M1030 M1102 M1103 Immediately Pause M1078 M1079 M1104 M1105