Delta DVP-ES2 — 3.8 Detailed Instruction Explanation

3. Instruction Set Program Example: 1. When X0 = ON, PLSR performs pulse output on Y0 with a target speed of 1000Hz, output pulse number D10 and ramp up/down time of 3000ms. Ramp up process begins to increase 1000/20 Hz in every shift and every shift outputs D10/40 pulses for 3000/20 ms. 2. When X0 = OFF, the output stops immediately and starts from the count value in D1030, D1031 when PLSR is executed again. 3. Ramp up/down shifts for Y0, Y2: 20. Ramp up/down shifts for Y1, Y3: 10 X0 Pulse speed(Hz) Target speed:1000 Hz Frequency increased/decreased in every shift: 1000/20 Hz 16-bit instruction:1~32,767 32-bit instruction:1~2,147,483,647 1 1 2 2 3 3 4 4 5 5 6 6 7 7 ... ...

19 19 20 20 Output pulses 20-shifts 20-shifts Ramp up time Time(Sec) Ramp down time Explanations on associated flags and registers: 3000ms 3000ms 1. Description on associated flags: For M1029, M1030, M1102, M1103, M1078, M1079, M1104, M1105, M1538, M1539, M1540, M1541, M1347, M1348, M1524, M1525, please refer to PLSY instruction. M1108: Y0 pulse output pause (ramp down). ON = pause, OFF = resume M1109: Y1 pulse output pause (ramp down). ON = pause, OFF = resume M1110: Y2 pulse output pause (ramp down). ON = pause, OFF = resume M1111: Y3 pulse output pause (ramp down).

ON = pause, OFF = resume 3-149 Series ES2/ ES2-C 12SA2/ ES2-E SS2 12SE 26SE 28SA2 EX2 SX2 Firmware version V3.42 V3.48 V1.00 V2.86 V3.28 -- V2.0 V3.0 SR K1000 D10 K3000 Y0 M1156: Enabling the mask and alignment mark function on I400/I401(X4) corresponding to Y0. M1257: Set the ramp up/down of Y0, Y2 to be “S curve.” ON = S curve. M1158: Enabling the mask and alignment mark function on I600/I601(X6) corresponding to