3. Instruction Set API 232~ 238 Operands: S 1 : Source device 1 S 2 : Source device 2 Explanations: 1. This instruction compares the content in S 1 and S 2 . Take API232 (AND =) for example, if the result is “=”, the continuity of the instruction is enabled. If the result is “≠”, the continuity of the instruction is disabled. 2. AND ※ ( ※ : =, >, , ≤, ≥) instruction is used for serial connection with contacts. 3. When the MSB (16-bit instruction: b15, 32-bit instruction: b31) of S 1 and S 2 is 1, the comparison value will be viewed as a negative value in comparison. 4. When 32-bit counters (C200 ~ C254) are used in this instruction, make sure to adopt 32-bit instruction (DAND ※ ).
If 16-bit instruction (AND ※ ) is adopted, a “program error” will occur and the ERROR indicator on the MPU panel will flash. Program Example: 1. When X0 = ON, and the content in C10 = K200, Y20 = ON 2. When X1 = OFF and the content in D0 ≠ K-10, Y21= ON and latched. X0 X1 3-503 Mnemonic Operands Function Controllers D AND※ Serial Type Comparison ES2/EX2 SS2 SA2 SX2 SE Type OP Bit Devices Word devices Program Steps X Y M S K H KnX KnY KnM KnS T C D E F AND※: 5 steps DAND※: 9 steps S 1 * * * * * * * * * * * S 2 * * * * * * * * * * * PULSE 16-bit 32-bit ES2/ EX2 SS2 SA2/ SE SX2 ES2/ SA2/ ES2/ SA2/ SS2 SX2 SS2 SX2 EX2 SE EX2 SE 16 -bit 32 -bit Continuity Discontinuity API No.
instruction instruction condition condition 232 AND= DAND= S 1=S 2 S 1≠S 2 233 AND> DAND> S 1>S 2 S 1≦S 2 234 AND< DAND< S 1<S 2 S 1≧S 2 236 AND<> DAND<> S 1≠S 2 S 1=S 2 237 AND<= DAND<= S 1≦S 2 S 1>S 2 238 AND>= DAND>= S 1≧S 2 S 1<S 2 AND= K200 C10 Y20 AND K-10 D0 SET Y21