Delta DVP-ES2 — 3.8 Detailed Instruction Explanation

DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming Operands: S 1 : Source device 1 S 2 : Source device 2 Explanations: 1. This instruction compares the content in S 1 and S 2 . Take API240 (OR =) for example, if the result is “=”, the continuity of the instruction is enabled. If the result is “≠”, the continuity of the instruction is disabled 2. OR ※ ( ※ : =, >, , ≤, ≥) instruction is used for parallel connection with contacts. 3. When the MSB (16-bit instruction: b15, 32-bit instruction: b31) of S 1 and S 2 is 1, the comparison value will be viewed as a negative value in comparison.. 4.

When 32-bit counters (C200 ~ C254) are used in this instruction, make sure to adopt 32-bit instruction (DOR ※ ). If 16-bit instruction (OR ※ ) is adopted, a “program error” will occur and the ERROR indicator on the MPU panel will flash Program Example: M60 will be ON either when both X2 and M30 are “ON”, or when the content in 32-bit register D100 (D101) ≥ K100,000. X2 M30 M60 3-504 API Mnemonic Operands Function Controllers 240~ 246 D OR※ Parallel Type Comparison ES2/EX2 SS2 SA2 SX2 SE Type OP Bit Devices Word devices Program Steps X Y M S K H KnX KnY KnM KnS T C D E F OR※: 5 steps DOR※:

9 steps S 1 * * * * * * * * * * * S 2 * * * * * * * * * * * PULSE 16-bit 32-bit ES2/ EX2 SS2 SA2/ SE SX2 ES2/ SA2/ ES2/ SA2/ SS2 SX2 SS2 SX2 EX2 SE EX2 SE 16-bit 32-bit Continuity Discontinuity API No. instruction instruction condition condition 240 OR= DOR= S 1=S 2 S 1≠S 2 241 OR> DOR> S 1>S 2 S 1≦S 2 242 OR< DOR< S 1<S 2 S 1≧S 2 244 OR<> DOR<> S 1≠S 2 S 1=S 2 245 OR<= DOR<= S 1≦S 2 S 1>S 2 246 OR>= DOR>= S 1≧S 2 S 1<S 2 DOR>= D100 K100000