Delta DVP-ES2 — 3.8 Detailed Instruction Explanation

3. Instruction Set Operands: S 1 : Timer number (T0~T255) S 2 : Setting value (K0~K32,767, D0~D9,999) 。 Explanations: 5. DVP-ES2/EX2 series PLCs whose version is 3.20/DVP-SS2 series PLCs whose version is 3.00/DVP-SA2 series PLCs whose version is 2.60/DVP-SE series PLCs whose version is 1.20/DVP-SX2 series PLCs whose version is v2.40 (or above) are supported. 6. When the instruction ATMR is executed, the coil of the timer specified is driven. When the timer value is equal to the setting value, the state of the normally-open contact is On, and the normally-closed contact is Off. Program Example: When the normally-open contact X0 is On, the timer T5 begins to measure time intervals.

If the timer value is larger than or equal to K1000, the normally-open contact Y0 will be On. Ladder diagram (The instruction TMR is used.) X0 T5 Y0 Ladder diagram (The instruction ATMR is used.) X0 Y0 3-505 API Mnemonic Operands Function Controllers 258 ATMR Contact type timer ES2/EX2 SS2 SA2 SX2 SE Type OP Bit Devices Word devices Program Steps X Y M S K H KnX KnY KnM KnS T C D E F ATMR: 5 steps S 1 * S 2 * * * PULSE 16-bit 32-bit ES2/ EX2 SS2 SA2 SE / SX2 ES2/ SA2/ ES2/ EX2 SS2 SA2/ SE SX2 SS2 SX2 EX2 SE Normally-open contact On Normally-closed contact Off TMR T5 K1000 ATMR T5 K1000