3. Instruction Set API 287~ 292 Operands: S 1 : Source device 1 S 2 : Source device 2 Explanations: 1. This instruction compares the content in S 1 and S 2 . Take “FOR =” for example, if the result is “=”, the continuity of the instruction is enabled. If the result is “≠”, the continuity of the instruction is disabled 2. The user can specify the floating point value directly into operands S 1 and S 2 (e.g. F1.2) or store the floating point value in D registers for further operation. 3. FOR ※ instruction is used for parallel connection with contacts. Program Example: When both X2 and M30 are On and the content in D100(D101) ≥ F1.234, M60 = ON..
X2 M30 M60 3-517 Mnemonic Operands Function Controllers FOR※ Floating Point Contact Type Comparison OR※ ES2/EX2 SS2 SA2 SX2 SE Type OP Bit Devices Word devices Program Steps X Y M S K H KnX KnY KnM KnS T C D E F FOR※: 9 steps S 1 * * * S 2 * * * PULSE 16-bit 32-bit ES2/ EX2 SS2 SA2/ SE E SX2 S2/ EX2 SS2 SA2/ SE SX2 ES2/ SA2/ SS2 SX2 EX2 SE API No. 32-bit instruction Continuity condition Discontinuity condition 287 FOR= S 1=S 2 S 1≠S 2 288 FOR> S 1>S 2 S 1≦S 2 289 FOR< S 1<S 2 S 1≧S 2 290 FOR<> S 1≠S 2 S 1=S 2 291 FOR<= S 1≦S 2 S 1>S 2 292 FOR>= S 1≧S 2 S 1<S 2 FOR>= D100 F1.234