Delta DVP-ES2 — 3.8 Detailed Instruction Explanation

DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming 295 Operands: S 1 : Communication port on a PLC S 2 : Function of a DMV D 1 : Source or destination device D 2 : Communication flag device Explanations: 1. The models supported are SS2 V3.2 and above. 2. S 1 specifies a communication port on a PLC for sending/receiving data and station numbers. Only the communication ports on a PLC are supported. Please refer to the description of the PLC used for more information. 3. S 1 +0 ~ S 1 +3 are described below. Description of S 1 +0: S 1 +0 ~ S 1 +1 Numbers must be used 4. S 2 is used to set a communication function code.

The devices that these operand occupies and the functions of the devices are described below. Remark Please refer to the description of the function codes below. It is only applicable to K0, and is not applicable to other codes. 0: Reading Other values: Writing It is only applicable to K0, and is not applicable to other codes. 3-518 Mnemonic Operands Function Controllers SS2 DMVRW DMV communication command Type OP Bit Devices Word devices Program Steps X Y M S K H KnX KnY KnM KnS T C D E F DMVRW:

9 steps S 1 * S 2 * D 1 * D 2 * * * PULSE 16-bit 32-bit ES2/ EX2 SS2 SA2/ SE SX2 ES2/ EX2 SA2/ SE SX2 ES2/ SA2/ SS2 SS2 SX2 EX2 SE Number Description Remark S 1+0 COM on a PLC Please refer to the description of a PLC. S 1+1 Station address of a DMV Applicable to a serial communication port (RS485/RS232/RS422) K1~K254 S 1+2, S 1+3 Reserved Reserved Communication port S 1+0 COM on a PLC K1~K5 K1~K5 represent PLC COM1~PLC COM5. Number Description S 2+0 Communication combination function code S 2+1 Communication address S 2+2 Reading/Writing