Delta DVP-ES2 — 2.13 Special Data Register

2. Programming Concepts 2-35 OFF STOP RUN Special ES2 SA2 Latch Content SS2 SX2    Attrib.

Default D EX2 SE -ed ON RUN STOP D1179 VR1 value ╳ ╳ ○ ○ 0 - - R NO 0 D1182 Index register E1 ○ ○ ○ ○ 0 - - R/W NO 0 D1183 Index register F1 ○ ○ ○ ○ 0 - - R/W NO 0 D1184 Index register E2 ○ ○ ○ ○ 0 - - R/W NO 0 D1185 Index register F2 ○ ○ ○ ○ 0 - - R/W NO 0 D1186 Index register E3 ○ ○ ○ ○ 0 - - R/W NO 0 D1187 Index register F3 ○ ○ ○ ○ 0 - - R/W NO 0 D1188 Index register E4 ○ ○ ○ ○ 0 - - R/W NO 0 D1189 Index register F4 ○ ○ ○ ○ 0 - - R/W NO 0 D1190 Index register E5 ○ ○ ○ ○ 0 - - R/W NO 0 D1191 Index register F5 ○ ○ ○ ○ 0 - - R/W NO 0 D1192 Index register E6 ○ ○ ○ ○ 0 - - R/W NO 0 D1193 Index register F6 ○ ○ ○ ○ 0 - - R/W NO 0 D1194 Index register E7 ○ ○ ○ ○ 0 - - R/W NO 0 D1195 Index register F7 ○ ○ ○ ○ 0 - - R/W NO 0 D1220 Pulse output mode setting of CH0 (Y0, Y1) ○ ○ ○ ○ 0 - - R/W NO 0 D1221 Pulse output mode setting of CH1 (Y2, Y3) ○ ○ ○ ○ 0 - - R/W NO 0 D1227 D1228 Sender’s IP address when executing ETHRS instruction in receiving mode (available for ES2-E:

V1.2, 12SE: V1.92, 26SE: V2.00) ES2-C ╳ SE ╳ 0 0 - R NO 0 D1229~ D1231 Network MAC address (hexadecimal format ex: 12:34:56:78:9A:BC => D1229=H'1234, D1230=H'5678, D1231=H'9ABC) (available for ES2-E: V1.2, 12SE: V1.92, 26SE: V2.00) ES2-C ╳ SE ╳ 0 0 - R YES 0 D1232* Number of output pulses for CH0 (Y0, Y1) ramp-down stop when mark sensor receives signals. (Low word). ○ ○ ○ ○ 0 0 -- R/W NO 0 D1233* Number of output pulses for CH0 (Y0, Y1) ramp-down stop when mark sensor receives signals. (High word). ○ ○ ○ ○ 0 0 -- R/W NO 0 D1234* Number of output pulses for CH1 (Y2, Y3) ramp-down stop when mark sensor receives signals. (Low word).

○ ○ ○ ○ 0 0 -- R/W NO 0 D1235* Number of output pulses for CH2 (Y2, Y3) ramp-down stop when mark sensor receives signals. (High word). ○ ○ ○ ○ 0 0 -- R/W NO 0 D1240* When interupt I400/I401/I100/I101 occurs, D1240 stores the low word of high-speed counter. ○ ○ ○ ○ 0 0 - R NO 0 D1241* When interupt I400/I401/I100/I101 occurs, D1241 stores the high Word of high-speed counter. ○ ○ ○ ○ 0 0 - R NO 0 D1242* When interupt I500/I501/I300/I301 occurs, D1242 stores the low Wordof high-speed counter. ○ ○ ○ ○ 0 0 - R NO 0 D1243* When interupt I500/I501/I300/I301 occurs, D1243 stores the high Word of high-speed counter.

○ ○ ○ ○ 0 0 - R NO 0 D1244 Idle time (pulse number) setting of CH0 (Y0, Y1) The function is disabled if set value≦0. ○ ○ ○ ○ 0 - - R/W NO 0 D1245 Idle time (pulse number) setting of CH1 (Y2, Y3) The function is disabled if set value≦0. ○ ○ ○ ○ 0 - - R/W NO 0 D1246* Low word of X2’s input pulse frequency (Unit: 0.01Hz) It is used with M1359. V3.22 ╳ ╳ V2.66 0 0 - R NO 0 D1247* High word of X2’s input pulse frequency (Unit: 0.01Hz) It is used with M1359. V3.22 ╳ ╳ V2.66 0 0 - R NO 0 D1249 Set value for COM1 (RS-232) data receiving time-out (Unit: 1ms, min.

50ms, value smaller than 50ms will be regarded as 50ms) (only applicable for MODRW/RS instruction) In RS instruction, no time-out ○ ○ ○ ○ 0 - - R/W NO 0