Delta DVP-ES2 — 3.8 Detailed Instruction Explanation

3. Instruction Set Operands S 1 : Station address of servo S 2 : The 1 st – segment speed S 3 : The 2 nd – segment speed Explanation 1. DZRNC instruction is supported for firmware V3.60 or later. 2. The INITC and ASDON (servo ON) instructions must be complete before this instruction is executed. 3. It is not available for pulse type instructions. Do not use pulse type contact. 4. The range of S 1 is K1–K8 (for servo). There will be no execution when the input value is out of the range. 5. For firmware V3.48 or earlier versions, this function is only available for ASDA-A2. The range for S 2 is 1-20000. The range for S 3 is 1-5000. The unit of the value of S 2 and S 3 is 0.1 rpm. 6.

For firmware V3.60 or later, this function is only available for ASDA-A3. When using rotary motor, the unit of the value of S 2 and S 3 is 0.1 rpm. The range of S 2 and S 3 is 1–60000, which indicates 0.1–6000.0 rpm. When using linear motor, the unit of the value of S 2 and S 3 is 10 -6 m/s. The range of S 2 and S 3 is 1-15999999, which indicates 0.000001-15.999999 m/s. 7. You need to use CASD instruction for acceleration and deceleration. 8. Once the target position is reached, the corresponding completion flags of axes M1624-M1631 will be set to ON. 9. Each ID has a corresponding register (D6032-D6047) to store the current position.

3-557 Mnemonic Operands Function Controllers ES2-C D ZRNC S 1, S 2, S 3 Servo homing Type OP Bit Devices Word devices Program Steps X Y M S K H KnX KnY KnM KnS T C D E F ZRNC: 7 steps DZRNC: 13 steps S 1 * * S 2 * * * S 3 * * * PULSE 16-bit 32-bit ES2-C ES2-C