DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming timeout is 0-3000 (default 200) and the unit is ms. If the receiving timeout time is set to 0, it indicates that the communication timeout is not limited and the status can be applied to the slave mode. 15. Descriptions on the Flags / Devices 3-584 Flags / Devices Default Descriptions M1620 OFF OFF CAN V2.0B protocol ON CAN V2.0A protocol M1621 / M1622 OFF/OFF OFF/OFF master mode: waiting to receive after sending; if you only need to send data, you can stop executing this instruction in the next scan. After sending is done, the slave response time should be longer than a scan cycle. OFF/ON master mode:
after sending in broadcast mode, receives data from multiple slaves until timeout occurs. ON/OFF slave mode: sending data, after receiving is done. ON/ON slave mode: only receiving in broadcast mode without responses M1623 OFF ON: communication error; PLC clears this flag when you start the instruction again. D1175 0 The accumulated packet number (slave number) in the broadcast mode; this number will be accumulated during execution. You can use this number when the completion flag is ON. Up to 100 slaves can be counted, when exceeding 100, the program does not save and stops counting. D1177 200 Timeout setting; the unit is ms.
When the value is set to 0, it indicates this function is disabled until this instruction stops executing. When the mode is in master broadcast, the timeout value cannot be 0. If the timeout value is 0, the system automatically adjusts this value to 200. When timeout occurs, it indicates the broadcast communication is over.