Delta DVP-ES2 — 5.3 The Operation of STL Program

DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming If M1014 is used, and M1040 is On, the steps in the same sequence will be cleared to Off. Ladder diagram: S0 S Driving the jumping of step S21 Using OUT S24 S X2 If M1040 is On, the state transfers to S21 in the OUT sequence. If X2 is On, the state of S21 will be cleared, ,and wil not be transferred to S24. S24 S23 S S24 S Returning to the initial step S25 Using OUT S0 S S0 X7 If M1040 is On, the state transfers to S25 in the OUT sequence. If X7 si On, the state of S25 will be cleared, and will not be transferred to S0. RET Cautions for Driving Output Point:

Once LD or LDI instructions are written into the second line after the step point, the bus will not be able to connect output coils directly otherwise errors will occur when compiling the ladder diagram. The following diagram explains the methods for correcting the ladder ion correct diagram. BUS Y0 S S n Y0 S S n Y0 S S n M0 Y1 Y2 or M0 Y1 Y2 M0 Y1 M1000 Y2 Modify the position of M0. Normally open contact in RUN mode Restrictions on Using Certain Instructions: Serial/parallel circuits or instructions in general ladder diagram are also applicable in step points of when using the instructions listed in the table below. STL diagram. However, there are restrictions on some of the instructions.

Care should be taken Basic Instructions Applicable in a Step 5-8 LD/LDI/LDP/LDF Basic instruction AND/ANI/ANDP/ANDF ANB/ORB MC/MCR OR/ORI/ORP/ORF MPS/MRD/MPP Step point INV/OUT/SET/RST Primary step point/ General step point Yes Yes No