5. Sequential Function Chart 1. DO NOT use MC/MCR instruction in the step. 2. DO NOT use STL instruction in a general subroutine or interruption subroutine. 3. CJ instruction can be used in STL instruction, however this is not recommended because the 4. Position of MPS/MRD/MPP instruction: actions will thus become more complicated. Ladder diagram: Instruction code: Explanation: STL Sn LD X0 MPS AND X1 OUT Y1 MRD AND X2 OUT M0 MPP AND X3 OUT Y2 MPS/MRD/MPP LD X0 MPS instruction cannot be Y1 S S n X1 X0 used directly on the new MRD X2 M0 bus. You have to execute BUS X3 LD or LDI instruction first MPP Y2 before applying MPS/MRD/MPP.
5-9 LD/LDI/LDP/LDF Basic instruction AND/ANI/ANDP/ANDF ANB/ORB MC/MCR OR/ORI/ORP/ORF MPS/MRD/MPP Step point INV/OUT/SET/RST Diverging step point/ Converging step point General output Yes Yes No Step point transfer Yes Yes No