7 CANopen Function and Operation DVP32ES2-C PC +24V L N NC X5 X1 S/S 24G X0 X3 X2 X4 X11 X7 X6 X10 X13 X12 X14 X15 X17 X16 RS-232 ZP1 ZP0 CAN+ SG + D D - CAN- Y5 UP0 Y0 Y1 Y3 Y2 Y4 Y10 Y7 Y6 UP1 Y12 Y11 Y13 Y16 Y15 Y14 Y17 ASDA-A2-xxxx-M TAP-CN03 CANopen CANopen The Corresponding Relation between Slave Parameter and Index/Subindex The index_subindex corresponding to P0-09 of servo is 2009_0. On the interface of the network configuration software, right click the servo icon; select “Parameter Edit” and then the following dialog box will appear. You can see the index_subindex corresponding to the servo parameter in the dialog box.
For more details on how to operate the network configuration interface, please refer to section 11.1.1 of the help file of CANopen Builder software. Explanation of Request Message Devices: 7-21 Content Explanation PLC device (Hex) High byte(Hex) Low byte(Hex) SDO request message mapping area D6250 0101 ReqID = 01 Command = 01 D6251 0004 Reserved Size = 04 D6252 0102 Type = 01 Node ID = 02 D6253 2009 Index high byte = 20 Index low byte = 09 D6254 0000 Reserved Subindex = 00