Delta DVP-ES2 — 7.5.2 CANopen Network Node State Display

7 CANopen Function and Operation  RUN indicator  ERROR indicator  COM3 ( CANopen ) Indicator 7.5.2 CANopen Network Node State Display  While the special auxiliary relay M1349 of DVP-ES2-C is ON, the CANopen function is enabled and D9980~D9998 will be used as the special registers as the table shows below. 7-23 LED indicator Description How to deal with The green light is on. PLC is running No resolution is required Light is off PLC is in stop status Make PLC run through RUN/STOP switch or WPLSoft LED indicator Description How to deal with Light is off PLC is normal No resolution is required The red light flashes.

There are syntax error existing in the program written to PLC or the PLC device or instruction is out of the allowed range. Judge the error cause according to the content value of the special register D1004 in PLC; find the program error position according to the content value of D1137. For more details on the error codes in D1004, please refer to “ES2 series PLC operation manual (Programming)”. The red light keeps on. PLC scan is timed-out Reduce the time for executing PLC program or use WDT instruction LED indicator Description How to deal with The green light keeps on. DVP-ES2-C is normal. No resolution is required The green light is in single flash. DVP-ES2-C stops.

The superior equipment is downloading the network configuration and waiting to complete downloading. The green light flashes. As DVP-ES2-C is in slave mode, it is preoperational; As DVP-ES2-C is in master mode, some slave is offline. 1. Check whether the wiring of the CANopen bus cable is correct. 2. Check whether the baud rate of the master is the same as that of the slave. 3. Check if the configured slaves have connected to the network. 4. Check if any slave is offline. The red light is in double flashes. The slave is off-line. 1. Check whether the CANopen bus cable is a standard one. 2. Check whether both ends of the CANopen bus are connected to the terminal resistors.

The red light in single flash. At least one error counter in the CAN controller reaches or exceeds the warning level. 1. Check whether the CANopen bus cable is a standard one. 2. Check whether both ends of the CANopen bus are connected to the terminal resistors. 3. Check whether there is much interference around the CANopen bus cable. The red light keeps on. Bus-off 1. Check whether the wiring of the bus cable in the CANopen network is correct. 2. Check whether the baud rate of the master is the same as that of the slave. Special register Function D9980 Used for displaying the state of DVP-ES2-C. D9981~D9996 Used for displaying the state of 16 nodes in the network