7 CANopen Function and Operation Code display in D9980 as DVP32ES2-C is in slave mode: 7.6 Application Example DVP-ES2-C is used to control Delta A2 servo rotation and monitor the actual rotation speed of motor in real time. The principle of operation is to map the relevant parameters of servo drive to the corresponding PDO and read or write the relevant parameters of servo drive through the CAN bus to accomplish the control requirement. Hareware Connection:
DVP32ES2-C PC +24V L N NC X5 X1 S/S 24G X0 X3 X2 X4 X11 X7 X6 X10 X13 X12 X14 X15 X17 X16 RS-232 ZP1 ZP0 CAN+ SG + D D - CAN- Y5 UP0 Y0 Y1 Y3 Y2 Y4 Y10 Y7 Y6 UP1 Y12 Y11 Y13 Y16 Y15 Y14 Y17 TAP-CN03 ASDA-A2-xxxx-M CANopen CANopen 7-25 Code Indication How to correct re-powering. F5 DVP-ES2-C setting error such as incorrect node address The node address of DVP-ES2-C should be set in the range: 1~127. F8 Internal error; the error is detected in the internal memory After re-powering, change into a new one if the error still exists. FB The sending buffer in DVP-ES2-C is full. Check if the CANopen bus cable is properly connected and then re-power. FC The receiving buffer in DVP-ES2-C is full.
Check if the CANopen bus cable is properly connected and then re-power. Code Indication How to correct A0 DVP-ES2-C is being initialized. -- A1 DVP-ES2-C is pre-operational. Check if the CANopen bus cable is properly connected A3 The data are being downloaded to DVP-ES2-C Wait to finish downloading the configured data. B0 Heartbeat message is timed-out Check if the CANopen bus cable is properly connected. B1 PDO data length returned from the slave is not consistent with the length set in the node list. Reset the PDO data length in the slave and download the new setting to DVPCOPM-SL. F4 BUS-OFF state is detected.
Check if CANopen bus cables are properly connected and ensure that all the node devices run at the same baud rate before re-powering. FB The sending buffer in DVP-ES2-C is full. Check if the CANopen bus cable is properly connected and then re-power. FC The receiving buffer in DVP-ES2-C is full. Check if the CANopen bus cable is properly connected and then re-power.