DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming Note: 1. We recommend user use the standard communication cable UC-DN01Z-01A (TAP-CB01) / UC-DN01Z-02A (TAP-CB02) / UC-CMC010-01A (TAP-CB10) and connect the terminal resistors such as Delta standard terminal resistor TAP-TR01 to either terminal of the network when constructing the network. 2. TAP-CN03 is a distribution box and the resistance it has can be effective after its SW1 is switched to ON. According to actual demand, user could select TAP-CN01/CN02/CN03 for wiring. 3. M of ASD-A2-xxxx-M refers to the model code and currently only the M-model servo supports CANopen communication. Setting Servo Parameters:
Set servo parameters as follows: Setting CANopen Baud Rate and Node ID of DVP-ES2-C DVP-ES2-C uses the default setting values: Node ID: 17 and baud rate: 1Mbps. CANopen Node ID and baud rate of DVP-ES2-C are set up through CANopen Builder software. See the detailed operation steps below: 1) Open CANopen Builder software and then click menu “Setup” > “Communication setting” > “System Channel”. 7-26 Parameter Setting Explanation 3-00 02 The Node ID of A2 servo is 2 3-01 400 CAN communication rate is 1Mbps. 1-01 04 Speed mode 0-17 07 Drive displays the motor rotation speed (r/min) 2-10 101 Set DI1 as the signal for Servo On 2-12 114 Set DI3 and DI4 as the signal for speed selection