DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming B.6.1 Setting the RTU Mapping (1) Enable Remote I/O Mapping selected, the network module used will be mapped onto RTU-EN01 according to the data Users can select the Enable Remote I/O Mapping checkbox. After the checkbox is set. (2) Communication Parameters Users can enter a time interval in the Communication Timeout box, and a cycle in the Update Cycle box. (3) PLC I/O Mapping Users can set the bit devices and the registers which correspond to digital inputs, digital outputs, and analog registers on RTU-EN01. The bit devices set start from M2000.
The registers used for the reading of data start from D2000, and the registers used for the writing of data start from D3000. The software automatically calculates end addresses according to the numbers set. (4) Setting the remote device mapping After users check an Enable cell, they have to enter the station address of RTU-EN01, an IP address, the number of digital inputs, the number of digital outputs, the number of registers used for the reading of data, and the number of registers used for the writing of data. DVPEN01-SL can be mapped onto four slaves.
The maximum number of digital inputs used for mapping, the maximum number of digital outputs used for mapping, the maximum number of registers used for mapping are described below. Digital I/O (RX+RY): 256 Analog (Reading) register: 64 Analog (Writing) register: 64 B-20