DVP-ES3 Series Programming Manual 3. Ramp-up and ramp-down for fixed slopes a) The following graph shows the Y0 output curve diagram. Frequency Target frequency Fixed slope Target frequency Original slope Start/end frequency Time b) Start the fixed slope flag SM469 and write the target frequency of the fixed slope into SR472. Ramp-up time Ramp-down time c) The new slope takes the place of the original slope and the DDRVI instruction performs the positioning as shown above. d) The general slope is determined by the start/end frequency, target frequency, and ramp up and down time.
The fixed slope is determined by the start/end frequency, target frequency of the fixed slope, and ramp up and down time. _6 e) When the target frequency of the fixed slope is less than the target frequency, the fixed slope function is not started. 4. Stop flag and immediately stop flag a) The following graphic shows the output diagram based on example 1. 6-796 Ramp-down stop Immediately stop