Delta DVP-ES3 — 6.26.2 Explanation of High-speed Output Instructions

Chapter 6 Applied Instructions b) Ramp-down stop  When M10 is ON, the DDRVI instruction is executed and starts to output pulses, and SM460, the Busy flag is ON.  When the instruction is disabled (M10 is OFF) or the stop flag SM463 is ON, the state of the immediately stop flag SM476 is confirmed.  If the immediately stop flag SM476 is OFF, the output ramps down to stop and then the Busy flag SM460 is OFF.  If M10 is not OFF and the stop flag SM463 is not ON after the instruction is executed, Y0 stops the output after 20,000 pulses. c) Immediately stop  If the instruction is disabled (M10 is OFF) or the stop flag SM463 is ON, the state of the immediately stop flag SM476 is confirmed.

 If the immediately stop flag SM476 is ON, the output stops immediately and the Busy flag SM460 is OFF. 5. Hardware limit function a) The following graphic shows the output curve diagram of axis 1 (Y0/Y1). 6_ b) Operation of the positive limit the positive limit function starts.  Positive limit input point X6 is set in HWCONFIG and downloaded to the PLC. When SM464 is set to ON,  DDRVI outputs 20,000 pulses in the positive direction. Note: the instruction does not output in the positive direction if the positive limit point is ON when the function starts. 6-797 Positive limit function Negative limit function