DVP-ES3 Series Programming Manual When the limit input point X6 is triggered by the external mechanism and is ON, the condition for the hardware positive limit function is met. DDRVI instruction stops the output immediately and the positive limit alarm SM465 is ON. If the condition for the hardware limit function is not met, Y0 stops the output after 20,000 pulses. c) Operation of the negative limit Negative limit input point X7 is set in HWCONFIG and is downloaded to PLC. When SM466 is set to ON, the negative limit function starts. DDRVI outputs 20,000 pulses in the negative direction. Note:
the instruction does not output in the negative direction if the negative limit point is ON when the function starts. When the limit input point X7 is triggered by the external mechanism and is ON, the condition for the hardware negative limit function is met. DDRVI instruction stops the output immediately and the negative limit alarm SM467 is ON. If the condition for the hardware limit function is not met, Y0 stops the output after -20,000 pulses. d) SM flags related to the limit function _6 Note: The limit point alarm flag is read-only and is set or reset automatically by the PLC according to the state of the start flag.
6-798 Axis number Axis 1 Axis 2 Axis 3 Axis 4 Enabling the hardware positive limit SM464 SM484 SM504 SM524 Positive limit alarm flag SM465 SM485 SM505 SM525 Enabling the hardware negative limit SM466 SM486 SM506 SM526 Negative limit alarm flag SM467 SM487 SM507 SM527