Chapter 6 Applied Instructions 6. Software limit function a) The following diagram shows the output curve diagram of axis 1 (Y0/Y1). b) Operation of the positive limit Positive software limit position is set in HWCONFIG (by setting SR580=11,000 for example). After downloading the setting to the PLC, it means the positive limit function starts. positive direction if the positive limit is exceeded when the function starts. DDRVI starts to output 20,000 pulses in the positive direction. Note: the instruction does not output in the When the current position SR460 > the limit position SR580, it means that the condition for the software limit 6_ function is met.
DDRVI instruction stops the output immediately and the positive limit alarm SM465 is ON. If the condition for the limit function is not met, Y0 stops the output after 20,000 pulses. 6-799 Positive limit function Negative limit function