Delta DVP-ES3 — 6.26.2 Explanation of High-speed Output Instructions

DVP-ES3 Series Programming Manual Example 1 X4 external interrupt program _6 Notes 1. When M0 changes from OFF to ON, Y0 starts to output pulses. After outputting more than 30,000 pulses, the external interrupt is detected on X4. The value in D0 increases by 1 and the pulse output stops after 15,000 pulses ( S 6 = 15,000). If the interrupt does not occur, the output does not stop until 100,000 pulses are output. 2. If the number of output pulses is between 1–30,000, they are in the fore mask section. The external interrupt occurs at X4 at the moment and the instruction does not perform the ramp-down stop operation. 3.

If the number of output pulses is between 70,000–100,000, they are in the rear mask section. The external interrupt occurs at X4 at the moment and the instruction still does not perform the ramp-down stop operation. 4. When the pulse output completes, SM461 is ON and M0 is reset. 6-814