Delta DVP-ES3 — 6.26.2 Explanation of High-speed Output Instructions

Chapter 6 Applied Instructions 3. S 4 is the target speed. The range is between 1–200,000Hz. 4. When the instruction executes the linear interpolation, the target frequency S 4 automatically corresponds to the output of the axis which is farthest from its target position. If X axis and Y axis cannot simultaneous reach the target positions, the PLC automatically decelerates the frequency to make the two axes reach the target positions simultaneously. 5. When the instruction is executed to modify parameters for the two axes (either of which is outputting), the modified parameters of the two axes are kept in the table and are not effective until the next 2-axis output starts. 6.

The parameters modified by the instruction can be modified only while the PLC is running. The last written parameter is not saved when the power turns OFF. The table that you edit in ISPSoft and download to the PLC is processed as the default position planning table when the power is ON. 6_ 6-857