Delta DVP-ES3 — 6.19.3 Descriptions of the Communication-related Flags and Registers

DVP-ES3 Series Programming Manual NOTE: the above flags are non-latching types. Communication-related registers (SR) _6 6-610 Flag Description Action COM1 COM2 SM209 SM211 Communication protocol changed flag The communication protocol changes in accordance with the setting values in SR. If the flag is set to ON, the communication protocol changes in accordance with the setting values in SR and then the system automatically resets the flag to OFF. NOTE: this change does not affect the parameters that you set in HWCONFIG. When the PLC is powered-on again, the PLC operates according to the communication protocol set in HWCONFIG. You set the flag to ON and reset it to OFF.

Special data register Description COM1 COM2 SR201 SR202 Communication port address SR209 SR212 Communication protocol For details, please refer to the following table to set up the communication format for a serial communication port. SR210 SR213 Communication timeout, unit: ms Suppose the setting value is larger than 0. When the PLC executes the communication instruction and is in the receiving state, but no data is received after the timeout period or the intervening time between two characters exceeds the setting value, the timeout flag is ON. You can set the register to 0 to disable communication timeout monitoring. See the MODRW instruction set between 100–32767 (ms).