Delta DVP-ES3 — 6.26.2 Explanation of High-speed Output Instructions

Chapter 6 Applied Instructions Refer to the following table for Attribute, Factory default and latched values of SM/SR corresponding to the axes. 6_ Note: R mean the device is readable. W means the device is writable. Wd means the device is writable any time except when performing the high-speed output.

6-793 Item Attribute StopRun RunStop Power ON Factory default Latched Busy flag R OFF OFF OFF OFF N Completion flag R / W OFF OFF OFF OFF N Stop flag R / W OFF OFF OFF OFF N Output completion R / W OFF OFF OFF OFF N auto-reset Enabling S curve R / W OFF OFF OFF OFF N ramp-up/down Enabling fixed slope R / W OFF OFF OFF OFF N ramp-up/down Executing an interrupt R / W OFF OFF OFF OFF N program when pulse output ends The output R / W OFF OFF OFF OFF N immediately stops when the instruction is disabled or stops Present output R / Wd No change No change No change 0 Y position Start/end R / Wd No change No change No change 200 Y frequency(Hz) Ramp-up time(ms) R / Wd No change No change No change 200 Y Ramp-down time(ms ) R / Wd No change No change No change 200 Y Target frequency of R / Wd No change No change No change 0 Y the fixed slope S curve mode R / Wd No change No change 0 0 N Present output R 0 0 0 0 N frequency