DVP-ES3 Series Programming Manual 8. After output completion auto-reset is enabled, the flag is automatically reset to OFF when the output completes. You must set the flag to ON again if the auto-reset function is needed for the next output operation. It is suggested that you use the rising-edge or falling-edge to trigger the flag every time. The function is usually used when the output DDRVI instruction cannot be scanned and executed by PLC program after DDRVI is executed. For example, when the instruction is executed in an interrupt program. 9.
If you use the Completion flag to set the I interrupt function, the flag is automatically reset to OFF when the output completes and the interrupt program starts. You must set the flag to ON again for the next output in which the interrupt occurs. It is suggested that you use the rising-edge or falling-edge to trigger the flag every time. 10. When the direction outputs are not using the default outputs to output, you can refer to the table below for setting up the time for directional outputting goes first before pulse outputting. So that you can be sure the outputting only happens when switching to the direction outputs. The unit for SR is millisecond and the range is 0-20 ms.
Default is 0, indicating inactive. Note: the time source here is from PLC scan time. Example 1 _6 When M10 is ON, Y0 outputs 20,000 pulses at 2 kHz (relative positioning). Y1 = OFF means the positive direction. 6-794 Output point for D1 Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 SR number SR640 SR641 SR642 SR643 SR644 SR645 SR646 SR647