User Manual EM303B General Purpose Inverter } else { crc_value = crc_value>>1; } } } return(crc_value); 12.5.5 Error Message Response Inverter will send an error message report when the master sends error data or inverter receives the error data due to the external interference. When Communication error occurs, slave combines the highest bit 1 of command code and error code as the response to the master. } Responding data frame format when errors happened in Communication: Responding command code at normal Communication and error Communication Description of Error Code For instance: Master sends data frame in hexadecimal format for F0-00to write 50.00HZ frequency. 181 ADU Item Byte No.
Range Error response: Address of slave 1 0~127 Error command code 1 The highest bit 1 of command code Error code 1 0x01~0x13 CRC parity(Low bytes go first) 2 Responding Command Code at Normal Responding Command Code at Error Communication Communication 03H 83H 06H 86H 10H 90H 08H 88H Error Description Error Description Code Code 01H Exceptional command code 06H Slave is busy 02H Exceptional data address 10H Frame error: Frame length error, parity error 03H Exceptional data 11H Parameter read only 04H Slave operation failure 12H Parameter is uneditable in operation. 05H Command enabled, in the process 13H Parameter is protected by password 01H 06H 00H 00H 13H 88H 84H 9CH