sinee — 7.3 F02 Group: Input Terminal Parameter

EM500 Open-Loop Vector Control Inverter User Manual 180 codes F15.03 - F15.13. 20 Acceleration/Decele ration Time Terminal 2 20 19 Acceleration/Deceleration Time 0 0 Group 1 (Acceleration Time: F00.14, Deceleration Time: F00.15) 0 1 Group 2 (Acceleration Time: F15.03, Deceleration Time: F15.04) 1 0 Group 3 (Acceleration Time: F15.05, Deceleration Time: F15.06) 1 1 Group 4 (Acceleration Time: F15.07, Deceleration Time: F15.08) 21 Acceleration/Decele ration Prohibited If the acceleration/deceleration time terminal is disabled, the command for acceleration/deceleration is prohibited and inverter’s output frequency remains the same.

If inverter is under the overcurrent protection status, run inverter as per current limit mode. 22 Operation Pause Inverter ramps to stop, but all running parameters are memorized, for example PLC parameter and PID parameter. If the terminal is disabled, inverter is reset to the pre-stop running status. 23 External Fault Input The fault signal of external devices can be inputted through this terminal, so that inverter monitors and protects peripherals at fault. Upon receiving external fault signal, inverter displays “E14”, and coast to stop. 24 Switch Run Command to Keypad Together with F00.02, these two terminals determine the present command channel. The priority rule is “24:

Switch Run Command to Keypad” > “25: Switch Run Command to Communication” > “F00.02: Command Source” (see F00.02). 25 Switch Run Command to Communication 26 Frequency Source Switching Mainly used with F00.06, and applied to the switching of the frequency source. This terminal works only when F00.06=3 – 5. See F00.06 for details 27 Clear Timed Running time This terminal is defined through F16.05 and used to clear the time that inverter has run (reset the remaining time of the timed run). See F16.05 for details. 28 Switch between The control mode of inverter is selected by these two terminals