EM500 Open-Loop Vector Control Inverter User Manual 182 information, please refer to the function code F09.18. 42 Process PID Integral When this terminal is enabled, the integral adjustment function of PID pauses, but proportional adjustment and differential adjustment of PID are still enabled, so this function is called “integral separation”. See F09.20 for details 43 PID Parameter Switching PID parameter switch is completed by the numeric input terminal (F09.11=2). If the terminal is Enabled, then PID parameters may be switched.
See F09.05 - F09.13 for details 44 PID Positive/Negative Action Switch When the terminal is enabled, inverter will switch between PID action mode and positive/negative action 45 Stop and DC Brake Trigger the stop command, and start braking when the start frequency of DC brake at stop (F04.20) is reached. The brake time shall be either terminal closing time or the time of DC brake at stop (F04.22), see whichever is longer. 46 DC Brake at Stop Not to trigger stop command. In case of stop command, start braking when the start frequency of DC brake at stop (F04.20) is reached. The brake time shall be either terminal closing time or the time of DC brake at stop (F04.22), see whichever is longer.
47 Immediate DC Brake After this terminal is enabled, inverter stops and starts DC brake at present frequency immediately. The brake current is determined by DC Brake Current at Stop (F04.21). 48 Fastest Coast-To-Stop When this terminal is enabled, inverter stops at the permitted fastest acceleration/deceleration time. 49 Not Used 50 External Stop Inverter stops as set stop mode (F04.19) and acceleration/deceleration time 4 (F15.07/F15.08) when this terminal is enabled.
51 Switch Main Frequency Source to Numeric Frequency Setting If this terminal is enabled, the main frequency source will be switched to corresponding setting under the conditions that main frequency source A is involved in setting and inverter is not in preset speed mode; functions of 51 to 56 may work independently, but have a priority sequence. See Table 7-1 of F00.04 for details. 52 Switch Main Frequency Source to AI1 53 Switch Main Frequency Source to AI2 54 Switch Main