EM500 Open-Loop Vector Control Inverter User Manual terminal’s output status is consistent with its function status; for monopulse output, the active level of certain pulse width can be output only when the function is enabled. This function code is of bit operation type. For specific settings, please refer to table 7-5 of the description part for F02.15. TT Pre- Output Active Inactive TTT TT TTTTT Positive Logic Output Active Level Inactive Level TTTT TTTT TTTTT Reverse Logic Sampling Active Level Inactive Level TTTT TTTT Figure 7-15 Positive and Negative Logic Output of Numeric Output Terminal According to the design, numeric multi-function output terminal status has two output logics: 0:
Positive logic, if the function is on, the multi-function output terminal outputs active level; if the function is off, the multi-function output terminal outputs inactive level. 1: Negative logic, if the function is on, the multi-function output terminal outputs inactive level; if the function is off, the multi-function output terminal outputs active level. This function code is of bit operation type. For specific settings, please refer to table 7-5 of F02.15. ★ This function is used for matching with the logic of other peripherals Actual level: Y1/Y2, the default active level is low level; the default actual level of R1/R2 is high level. 199 No.
Function Range Unit Default Type F03.06 Positive/Negative Logic of Numeric Output D7 D6 D5 D4 D3 D2 D1 D0 00000 〇 * * * Y3 R2 R1 Y2 Y1 0: Positive Logic, Enabled at On/Disabled at Off 1: Negative Logic, Disabled at On/Enabled at Off No. Function Range Unit Default Type F03.07 Y2 Output Type 0: Common Numeric Output 1: High-Frequency Pulse Output 0 〇