sinee — 7.4 F03 Group: Output Terminal Function Parameter

EM500 Open-Loop Vector Control Inverter User Manual The terminal will delay to response according to the function code setting when the function terminal changes. At present, terminals Y1/Y2 and R1/R2 support this function. Specific actions: corresponding output terminal outputs active level only when the function terminal changes from disabled status to enabled status and the effective delay time is reached; corresponding output terminal outputs inactive level only when the function terminal changes from enabled status to disabled status and the ineffective delay time is reached. ★ If the function code is set as 0.000s, the delay function will be disabled.

user may control the active level pulse width by setting monopulse output time to meet When the output type of a function output terminal is monopulse output (see F03.05), various process or control requirements. See Figure 7-14 and Figure 7-16 for details. M1 and M2 are 2 multi-function analog output terminals and Y2 can be set as a high-speed pulse output terminal (F03.07=1). By setting the function codes F03.21 - F03.23, user may define the functions of output terminals. For example, if F03.21=0, the function of M1 terminal is to output “Running frequency (absolute value)”, and reflects present value of “Running frequency” (absolute value)” by outputting different voltage values.

If the running frequency increases from 201 No. Function Range Unit Default Type F03.17 Y1 Output Monopulse Time 0.001 - 30.000 s 0.250 ● F03.18 Y2 Output Monopulse Time 0.001 - 30.000 s 0.250 ● F03.19 R1 Output Monopulse Time 0.001 - 30.000 s 0.250 ● F03.20 R2 Output Monopulse Time 0.001 - 30.000 s 0.250 ● No. Function Range Unit Default Type F03.21 Analog Output M1 See Table 7–7 Multi-Function Analog Output Terminals 0 〇 F03.22 Analog Output M2 2 〇 F03.23 Y2 High-Frequency Pulse Output Function 11 〇