sinee — 7.4 F03 Group: Output Terminal Function Parameter

EM500 Open-Loop Vector Control Inverter User Manual 0.00 Hz to 50.00 Hz (assuming F00.16=50.00), then the default condition is that the M1 output voltage increases from 0.00V to 10.00 V, with the same variation trend as that of the running frequency. Specific functions available are shown in Table 7-7.

Table 7–7 Multi-Function Analog Output Terminals ★ Fmax, Maximum Frequency (F00.16) Ie, Inverter Rated Current (F12.21) 202 Value Function Description 0 Running frequency (absolute value) 0.00 Hz - Fmax, corresponding output 0.0% - 100.0% 1 Set frequency (absolute value) 0.00 Hz - Fmax, corresponding output 0.0% - 100.0% 2 Output torque (absolute value) 0.0% - 200.0%, corresponding output 0.0% - 100.0% 3 Set torque (absolute value) 0.0% - 200.0%, corresponding output 0.0% - 100.0% 4 Output Current 0.0A - 2*Ie, corresponding output 0.0% - 100.0% 5 Output Voltage 0.0V - 1.5*Ue, corresponding output 0.0% - 100.0% 6 Bus voltage 0V - 1000V, corresponding output 0.0% - 100.0% 7 Output Power 0.00kW - 2*Pe, corresponding output 0.0% - 100.0% 8 AI1 Output the actual input voltage, other than the results after offset 0.0% - 100.0%, corresponding output 0.0% - 100.0% 9 AI2 10 AI3 11 AI4 (Expansion Card) 12 High-Speed Pulse Input F02.26 - F02.28, corresponding output 0.0% - 100.0% 13 Not Used 14 The Count Value 0~F16.03 corresponding output F16.10~F16.11 15 Length Value 0~F16.01 corresponding output F16.10~F16.11 16 The PID Output Percentage -100.0%~100.0% corresponding output 0.0%~100.0% 18 PID Feedback -100.0%~100.0% corresponding output 0.0%~100.0% 19 PID Is Given -100.0%~100.0% corresponding output 0.0%~100.0% 20~37 Not Used 38 The Fan Speed Output Air compressor special function0%~100% Corresponding to the maximum frequency inverter for fan