EM500 Open-Loop Vector Control Inverter User Manual Ue, Inverter Rated Voltage (F12.20) Pe, Inverter Rated Power (F12.19) The output of the analog output terminal can be switched through DIP between the voltage signal 0.00V - 10.00 V and the current signal 0.00mA - 20.00mA. For voltage signal, 0.0% - 100.0% corresponds to the output 0.00V - 10.00 V; for current signal, 0.0% - 100.0% corresponds to 0.00mA - 20.00mA. See 3.3.7 Analog Output Terminal Wiring for details. High-Frequency Pulse Output Rating:
As indicated in Table 7-7, for output of 100.0%, the setting shall correspond to maximum output frequency; for output of 0.0%, the setting shall correspond to minimum output frequency; output between 100.0% and 0.0% maintains a linear relationship with setting values. F03.26 performs first-order inertia filter with respect to output. These function codes are used to correct the zero shift and output amplitude deviation of the analog output generally, and they can also be used to define the desired AO output curve to meet different instrument or other requirements. If use “b” for offset, “k” for gain, “Y” for actual output, and “X” for standard output, then the actual output is: Y=kX + b.
203 No. Function Range Unit Default Type F03.24 Maximum Frequency of Y2 High-Frequency Pulse Output 0.00 - 100.00 kHz 50.00 ● F03.25 Minimum Frequency of Y2 High-Frequency Pulse Output 0.00 - 100.00 kHz 0.00 ● F03.26 Filter Time of Y2 High-Frequency Pulse Output 0.00 - 10.00 s 0.10 ● No. Function Range Unit Default Type F03.27 M1 Output Offset -100.0 - 100.0 % 0.0 ● F03.28 M1 Output Gain -10.00 - 10.00 1.00 ● F03.29 M2 Output Offset -100.0 - 100.0 % 0.0 ● F03.30 M2 Output Gain -10.00 - 10.00 1.00 ●