EM500 Open-Loop Vector Control Inverter User Manual this time immediately may result in overcurrent fault. In order to avoid such a fault, add the link of DC brake at first prior to inverter start to stop motor, and then start inverter to the set frequency according to the set direction. Different values of F04.03 may realize different start DC brake torques. By setting the action time of DC brake through F04.04, inverter starts immediately after the set time is out. If F04.04=0.00, DC brake is disabled at start. ★ The process of starting DC brake is shown in Figure 7-18.
This function may be enabled when the single inverter serves multiple motors and inverter is starting running after the set pre-excitation time (F04.07) is out. If the set pre-excitation is 0, Inverter develops a magnetic field as the set pre-excitation current, and starts inverter will start directly without the pre-excitation link. F04.06 pre-excitation current is a percentage relative to motor’s rated no load current. When the starting mode is selected as the torque tracking start (F04.00=1), inverter will perform the torque tracking as per the setting through F04.08 at start.
Please select a proper mode according to the working condition, so as to better track present motor running frequency. 205 No. Function Range Unit Default Type F04.06 Pre-Excitation Current 50.0 - 500.0 (100.0=Idling Current) % 100.0 〇 F04.07 Pre-Excitation Time 0.00 - 10.00 s 0.10 〇 No. Function Range Unit Default Type F04.08 Rotation Speed Tracking Method 0: Start from Maximum Frequency 1: Start from Stop Frequency 2: Start from Power frequency 0 〇