EM500 Open-Loop Vector Control Inverter User Manual This mode can be selected when inverter starts tracking downwards from the maximum frequency (F04.08=0) and the running status of motor is completely unsure (motor is in rotation status when inverter is powered on). ; If F04.08=1, it means that inverter starts tracking from the stop frequency. Generally, this mode is selected; If F04.08=2, it means that inverter starts tracking from the power frequency. This mode can be selected if the power frequency changes to the frequency conversion. F04.09: Rise Speed of Rotation Speed Tracking Voltage. F04.10:
The scanning speed starting from the set frequency to downward tracking at the torque tracking; this time refers to the period that the rated frequency decreases to 0.00 Hz. F04.11: Tracking current, which is a ratio relative to inverter rated current. The lower the current is, the smaller the impact of motor will be, so is the tracking accuracy. However, if the current is set as an excessively low value, the tracking results may be inaccurate, which result in the start failure. The higher the current is, the fewer motor rotation speed drop at tracking will be; please increase the set value for heavy load tracking occasions. F04.12: Tracking intensity.
Generally, the default is usually adopted. This value may be increased when the tracking speed is high and results in a voltage fault. 206 No. Function Range Unit Default Type F04.09 Rise Time of Rotation Speed Tracking Voltage 0.05 - 10.00 s 0.30 〇 F04.10 Deceleration Time of Rotation Speed Tracking 0.1 - 20.0 s 2.0 〇 F04.11 Rotation Speed Tracking Current 30.0 - 150.0 (100.0=Inverter Rated Current) % 60.0 ● F04.12 Rotation Speed Tracking Compensation Gain 1.00 - 1.30 1.05 ● Defaul No. Function Range Unit Type t F04.14 Acceleration/Decel eration Mode 0: Linear Acceleration/Deceleration 1: S Curve Acceleration/Deceleration 0 〇 F04.15 S Curve Start 0.00 - System acceleration time/2 s 1.00 ●