EM500 Open-Loop Vector Control Inverter User Manual TT TT Output Frequency Linear Acceleration/ Deceleration TT TTT S Curve Acceleration STT TTT / Deceleratio n Deceleration Time t3 t4 TTTT 7-17 Acceleration/Deceleration Time Control F04.19=0: Ramp-To-Stop Motor ramps to stop after the set deceleration time is out [default setting is as per F00.15 (deceleration time 1)] F04.19=1: Coast-to-Stop After enabling the stop command, inverter will stop output immediately and motor will coast to stop. Specific stop time depends upon the inertia of motor and the load.
If the coast-to-stop terminal is set, inverter coasts to stop immediately after the coast-to-stop terminal is enabled; inverter will not run again even if the terminal is disabled unless a run command is inputted. 208 t1 t2 t2 AccelTeraTtioTnT Time No. Function Range Unit Default Type F04.19 Stop Mode 0: Ramp-To-Stop 1: Coast-to-Stop 0 〇 No. Function Range Unit Default Type F04.20 DC Brake Start Frequency at Stop 0.00 - Maximum Frequency F00.16 Hz 0.00 〇 F04.21 DC Brake Current at Stop 0.0-150.0 (100.0= Motor Rated Current) % 100.0 〇 F04.22 DC Brake Time at Stop 0.00 - 30.00, Disabled at 0.00 s 0.00 〇 F04.23 DC Brake Field 0.00 - 30.00 s 0.50 〇