sinee — 7.5 F04 Group: Start/Stop Control Parameter

EM500 Open-Loop Vector Control Inverter User Manual F04.20 set the starting DC brake frequency during ramp-to-stop. During ramp-to-stop, once output frequency is lower than this value, inverter will start DC brake if the DC brake time at stop is not set as 0. Different values of F04.21 may realize different DC brake torques at stop. F04.22 is used to set the action time of DC brake at stop. If F04.22=0.00, DC brake at stop will be disabled. If there is also a signal of DC brake from an external terminal, then the DC brake time at stop shall be the bigger of the following two: the action time of DC brake signal of an external terminal, and the time set through F04.22.

the value set through F04.20 and the time set by F04.24 is reached. For 04.23, inverter starts DC brake in ramp-to-stop when output frequency reaches The process of DC brake at stop is shown in Figure 7-19. Figure 7-18 Start Process of DC Brake Figure 7-19 Stop Process of DC Brake Generally, for a heavy load, the deceleration operation may not stop motor completely after the deceleration time is out due to inertia; extending the DC brake time at stop or increasing DC brake current at stop can stop motor 209 Weakening Time at Stop