sinee — 7.5 F04 Group: Start/Stop Control Parameter

EM500 Open-Loop Vector Control Inverter User Manual When magnetic flux brake is enabled (F04.24>100), inverter may enable motor for rapid deceleration by the method of increasing the magnetic flux of motor. At this time, the electric energy in motor brake process can be transformed into thermal energy The magnetic flux brake can be used to realize the rapid deceleration, but output current may be large; user may set the magnetic flux brake intensity (F04.24) for limit protection so as to avoid damaging motor; if the magnetic flux brake is disabled, the deceleration time will be long, but output current is small.

setting of F04.00 (F04.26=0) , but user may select the torque tracking start (F04.26=1) in As for the start mode after fault or coast to stop, the default is the start as per the a fixed way. For various stop modes, see the function code F04.00. F04.27=0: Not to Confirm If the running terminal (RUN or F/R) is on and F00.03 is set as 0 or 1, inverter is powered on while enabling or disabling the terminal, or inverter runs directly while the start/stop mode is switched to the terminal. F04.27=1 : Confirm Close running terminal, set F00.03 as 0 or 1, inverter cannot run directly when start or stop by the terminal at power-on or when the starting or stop mode is switched to terminal mode.

210 No. Function Range Unit Default Type F04.24 Magnetic Flux Brake Gain 100 – 150 (100: No Magnetic Flux Brake) 100 〇 No. Function Range Unit Default Type F04.26 Start Mode after Fault/Coast to Stop 0: Start as per the Set Mode of F04.00 1: Rotation Speed Tracking Start 0 〇 No. Function Range Unit Default Type F04.27 Terminal Start Command Reconfirmation 0: Not to Confirm 1: Confirm 0 〇