EM500 Open-Loop Vector Control Inverter User Manual When present motor is a synchronous motor (eg: F01.00=2) and in the VF control mode, the initial angle is crucial to the control performance; especially, motor may reverse at the moment of start. Therefore, the default of inverter is to perform the initial position search after power-on or fault, so as to obtain better control performance. 7.6 F05 Group: VF Control Parameter This group of function codes is only valid for V/F control and not valid for vector control.
“one inverter shared by multiple motors” or the occasion where there is high difference V/F control applies to the general loads like fan and water pump, or to the occasion between inverter power and motor power F05.00=0: Straight Line V/F Applies to general constant torque load F05.00=1: Multi-Pot V/F parameters of F05.01 - F05.06, user may obtain a user-defined V/F curve. Applicable for dehydrator, centrifuge, crane and other special loads. By setting F05.00=2/3: VF to the 1.3rd / VF to the 1.7th Refers to a VF curve that goes between the linear VF and the square VF. 211 No. Function Range Unit Default Type F04.30 Initial Position Search after Power-on or Fault 0: Disabled 1:
Enabled 0 ● No. Function Range Unit Default Type F05.00 V/F Curve Setting 0: Straight Line V/F 1: Multi-Dot Polyline V/F 2: VF to the 1.3rd 3: VF to the 1.7th 4: Square V/F 5: VF Complete Split Mode (Ud=0, Uq=K*t=Split voltage source voltage) 6: VF Half-Split Mode (Ud=0, Uq=K*t=F/Fe*2*Split voltage source voltage) 0 〇