sinee — 7.6 F05 Group: VF Control Parameter

EM500 Open-Loop Vector Control Inverter User Manual F05.00=4: Square V/F Applies to centrifugal loads like fan and water pump. F05.00=5: VF Complete Split Mode Inverter output frequency and output voltage are independent, with output frequency determined by the frequency source and output voltage determined by F05.07 (Voltage Source of VF Separation Mode). This mode is generally used for occasions such as induction heating, inversion power supply and torque motor control. F05.00=6: VF Half-Split Mode In this mode, V and F are proportional.

However, the proportion can be set through the power supply source (F05.07) and this proportion has something to do with motor rated voltage and rated frequency of F1 group. output voltage V and frequency F is as follows: Assuming that the power supply source is X (0 - 100%), the relationship between V/F=2*X* (motor rated voltage) / (motor rated frequency) Parameters of the function codes F05.05 - F05.10 will be enabled if Multi-Dot Polyline V/F is selected (F05.00=1). A user-defined V/F curve is determined by the curve set with the input frequency percentage and output voltage percentage, and it is linearized at different segments in different input ranges.

Motor rated frequency is the ultimate frequency reached by the V/F curve and also 212 No. Function Range Unit Default Type F05.01 Multipoint VF Frequency Point F1 0.00 - F05.03 Hz 0.50 ● F05.02 Multipoint VF Voltage Point V1 0.0 - 100.0 (100.0= Rated Voltage) % 1.0 ● F05.03 Multipoint VF Frequency Point F2 F05.01 - F05.05 Hz 2.00 ● F05.04 Multipoint VF Voltage Point V2 0.0 - 100.0 % 4.0 ● F05.05 Multipoint VF Frequency Point F3 F05.03 - Motor Rated Frequency (Reference Frequency) Hz 5.00 ● F05.06 Multipoint VF Voltage Point V3 0.0 - 100.0 % 10.0 ●