sinee — 7.6 F05 Group: VF Control Parameter

EM500 Open-Loop Vector Control Inverter User Manual the frequency at maximum voltage output. The input frequency percentage: if motor rated frequency is the input frequency, the percentage is 100.0%; output voltage percentage: if motor rated voltage is output voltage (U e ), the percentage is 100.0%. The relationship between the three voltage points and the frequency point must meet the following requirements: V1 An excessive slope of the V/F curve may result in an “overcurrent” fault. Especially, an excessively high voltage at low frequency may cause motor to be overheated or burn motor and inverter may get in overcurrent stall or overcurrent protection.

Output Voltage (%) Motor Rated Voltage V3 V2 V1 Output Frequency (%) Motor Rated Frequency Figure 7-20 Multi-Dot Polyline V/F Curve F1 F2 F3 The VF separation is generally used for occasions such as induction heating, inversion power supply and torque motor control. 213 No. Function Range Unit Default Type F05.07 Voltage Source of VF Separation Mode 0: Numeric Setting of VF Separation Voltage 1: AI1 2: AI2 3: AI3 4: High-Frequency Pulse (X7) 5: PID 6: Communication Percentage Setting Note: Motor Rated Voltage is 100% 0 〇 F05.08 Numeric Setting of VF Separation Voltage 0.0 - 100.0 (100.0=Motor Rated Voltage) % 0.0 ●