EM500 Open-Loop Vector Control Inverter User Manual In VF separation control, output frequency can be set by F05.08 as well as analog input, high speed pulse, PID or communication setting. In nonnumeric setting, 100% of each setting refers to motor’s rated voltage. When the set percentage of analog output is negative, then take the set absolute value as effective value. F05.07=0: Numeric Setting of VF Separation Voltage (F05.08) VF separation output voltage is determined by the numeric setting of VF separation voltage (F05.08). F05.07=1: AI1 F05.07=2: AI2 F05.07=3: AI3 F05.07=4: High-Frequency Pulse Input (X7) Setting of VF Separation Voltage (F05.08).
VF separation output voltage is determined by AI/HDI (percentage) * Numeric Please refer to the description of F00.04 for detailed explanations of AI1-AI3 and X7. F00.04 has the same meanings as AI1-AI3 and X7. 100.00% is the percentage inputted through F05.08 (Numeric Setting of VF Separation Voltage). F05.07=5: Process PID VF separation output voltage is determined by the process PID (see 7.10). F05.07=6: Communication Percentage Setting The VF separation output voltage is determined through communication.
If inverter is under master-slave communication control (F10.05=1) and present inverter is a slave (F10.06=0), the VF separation output voltage is set as “700FH (Communication Percentage Setting) * F01.02 (Motor Rated Voltage) * F10.08 (Receiving Proportionality Factor of Slave)”. The range of 700FH is 0.00% to For general communication (F10.05=0), VF separation output voltage is set as 100.00%. See Table 12-2 for details. “7006H (VF separation mode voltage setting) * F05.08 (Numeric Setting of VF Separation Voltage)”. The range of 7006H is 0.00% to 100.00%. See Table 12-2 for details. 214