EM500 Open-Loop Vector Control Inverter User Manual The voltage rise time of VF separation is the time that the voltage increases from 0 to motor rated voltage. Output Voltage Motor Rated Voltage VF Separation Voltage TTTTTT Actual Rise Time t 0 TTTTTT Set Rise Time Figure 7-21 Voltage Rise Time of VF Separation This function code is used to compensate for the voltage drop generated by the rotor resistor and cable, and promote the loading capacity at low frequency of inverter. When rotor’s speed drops by an increase of load, to ensure the rotor’s speed is close to synchronous speed under rated load, slip compensation can be applied, increase the setting value of F05.11.
★ If F05.11 = 0, the slip compensation is disabled; this parameter is only enabled for the synchronous motor. When inverter makes a quick start under large inertia, the slip is 100%; after reaching the set frequency, the slip is 0; quick decrease of output frequency would result in overvoltage or overcurrent. F05.02 may mitigate the boost of voltage and current. 215 No. Function Range Unit Default Type F05.09 Rise Time of VF Separation Voltage 0.00 - 60.00 s 2.00 ● No. Function Range Unit Default Type F05.10 V/F Stator Voltage Drop Compensation Gain 0.00 - 200.00 % 100.00 ● No.
Function Range Unit Default Type F05.11 V/F Slip Compensation Gain 0.00 - 200.00 % 100.00 ● F05.12 V/F Slip Filter Time 0.00 - 10.00 s 1.00 ●