sinee — 7.11 F10 Group: Communication Function Parameter

EM500 Open-Loop Vector Control Inverter User Manual As a slave when connected to the whole communication network, inverter must have a unique address, for which the setting scope is 1 to 247. That is to say, 247 inverters are supported by one network. ★ 0 is a broadcasting address, which can be recognized by all inverters and does not need to be set specifically. All masters and slaves connected to the same network must follow the same transmission principles (for example bit rate, data format and protocol format) to ensure the normal communication. Therefore, the settings for F10.01 (bit rate), F10.02 (data format) and F10.10 (communication protocol; default:

Modbus-RTU protocol for EM500) for all devices connected to the network are the same. EM500 Inverter supports 6 bit rates (unit: bit/s) when it is in Modbus-RTU communication. If F10.01=9600 bps, it means that 9600 bits will be transmitted for each second. Under default conditions, to transmit each byte of valid data (for example 0x01), the actual transmission is 10 bits and the time needed is about 1.04 ms (about 1.04167 ms=10bit/9600 bps). 252 No. Function Range Unit Default Type F10.00 Inverter Address 1 - 247, 0 as broadcasting address 1 〇 No. Function Range Unit Default Type F10.01 Modbus Communicatio n Bit Rate 0: 4800 1: 9600 2: 19200 3: 38400 4: 57600 5: 115200 bps 1 〇 No.

Function Range Unit Default Type F10.02 Modbus Data Format 0: 1-8-N-1 (1 start bit + 8 data bits +1 stop bit) 1: 1-8-E-1 (1 start bit + 8 data bits + 1 even parity + 1 stop bit) 2: 1-8-O-1 (1 start bit + 8 data bits + 1 odd parity + 1 stop bit) 3: 1-8-N-2 (1 start bit + 8 data bits +2 stop bits) 0 〇