sinee — 7.11 F10 Group: Communication Function Parameter

EM500 Open-Loop Vector Control Inverter User Manual different data formats according to data combinations. When transmitting data via When transmitting data via Modbus protocol of RTU format, inverter supports 6 Modbus protocol of RTU format, inverter supports 6 different data formats according to data combinations. If F10.02=0, it means that present data format is 1 start bit + 8 data bits + no parity +1 stop bit ★ N (NONE), no parity; E (EVEN), even parity; O (ODD), odd parity. Inverter also supports the functions of communication overtime and response delay, when it is networked for communication with Modbus protocol, in order to meet various requirements.

As shown in Figure 7-30, the communication interval △ t refers to the period from the previous receipt of a valid data frame by slave (inverter) to the receipt of a valid data frame again. If △ t is greater than the set time (see F10.03; this function is disabled if it is set as 0), this is called “communication overtime”. 1# 2# 3# 1# Sen d Return Retur n Send Return Send Return Figure 7-30 Communication Overtime Tt Application example: If master must send data to a slave (for example #1) within a certain time T, then user may enable the communication overtime function for #1 slave 253 4: 1-8-E-2 (1 start bit + 8 data bits + 1 even parity +2 stop bits) 5:

1-8-O-2 (1 start bit + 8 data bits + 1 odd parity +2 stop bit) Start bit Valid data Parity Stop bit 1 7 6 5 4 3 2 1 0 N/O/E 1 No. Function Range Unit Default Type F10.03 Modbus Overtime 0.0 - 60.0, 0.0: Disabled (also works for master - slave system) s 0.0 ●