EM500 Open-Loop Vector Control Inverter User Manual by setting F10.03>T. No fault report for the communication overtime will be triggered during normal communication. However, if master does not send data to #1 slave for a time period T and this condition is maintained for a time set by F10.03, then a communication abnormality fault (E16) will be reported to notify the personnel of “#1 slave communication fault”, so that the personnel may conduct troubleshooting. ★ The time set by F10.03 must be greater than T, but must not be excessive, otherwise the running of inverter under a fault condition for a long time may result in adverse effects.
set up the parameters, used to monitor the communication status. ★ F10.03 should be disable normally. Only in the continuous communication system, Define the time interval from the receipt of valid data frame 1 by inverter, to data learning, and then to starting the data return, as the response delay (t w2 ). To ensure that the protocol chip works stably, the response delay shall be set as 1 ms to 20 ms (no 0). If the communication data involves EEPROM, the actual response delay will be extended to “EEPROM action time + F10.04” 1: valid data frame: sent by the external master to inverter, and the function code, data length and CRC are correct.
As shown in Figure 7-31, data sending section (t s ), sending end mark section (t w1 ), 75176 forwarding waiting section (t w2 ), data return section (tr) and 75176 receipt section (t w3 ). 254 Function Name of Parameter Description Unit Default Property Code Function Code F10.04 Modbus Response Delay 1 - 20 ms 2 ●