EM500 Open-Loop Vector Control Inverter User Manual t w3 t t s t w1 t w2 tr Figure 7-31 Complete Data Frame Time Sequence Translation EM500 supports master-slave communication function. In master-slave communication, one inverter is used as master while other inverters are slaves; all slaves work as the command sent by master to achieve the synchronous running function of multiple inverters. For master, inverter will be set as follows: Set F10.05=1 to enable master-slave function; Set F10.06=1 or 2 to set present inverter as master (only one inverter can be used as 255 No. Function Range Unit Default Type F10.05 Master-Slave Communication Function 0: Disabled 1:
Enabled 0 〇 F10.06 Master-Slave Options 0: Slave 1: Master (Modbus protocol) 2: Master (CANSinee protocol) 0 〇 F10.07 Data Sent by Master 0: Output Frequency 1: Set Frequency 2: Output Torque 3: Set Torque 4: PID Setting 5: Output Current 1 〇 F10.08 Receiving Proportionality Factor of Slave 0.00 - 10.00 (Times) 1.00 ● F10.09 Sending Interval of Master 0.000 - 30.000 s 0.200 ●