sinee — 7.11 F10 Group: Communication Function Parameter

EM500 Open-Loop Vector Control Inverter User Manual master in a network); F10.07 is used to set the variable needing synchronization; for example output  For a slave, inverter will be set as follows: current, set F10.07=5. Set F10.05=1 to enable master-slave function Set F10.06=0 to select present inverter as a slave ; Set a setting as communication setting; for example, if F09.00=6, and the process PID is set individually (F00.05=10 and F00.06=1), slave inverter will take output current of master as the setting for PID regulation.

For a slave, F10.08 can be used to determine how inverter makes use of the received data.If F10.08=0.80, the finally used data is “Recv (Received Data) * 0.80 (F10.08)”. For master, F10.09 can be used to determine how long a command is sent by master. EM500 inverter supports multiple communication protocols. Except inverter for Modbus-RTU, user must buy an expansion card of the company independently. Please contact your dealer if necessary. For communication expansion card address setting, user only needs to set 256 No. Function Range Unit Default Type F10.10 Communication Protocol 0: Modbus-RTU Protocol 1: Profibus-DP Protocol 2: CANopen Protocol 3: DeviceNet Protocol 0 〇 No.

Function Range Unit Default Type F10.11 Communication Address of Profibus-DP Expansion Card 1 - 125 1 〇 F10.12 Communication Address of CANopen Expansion Card 1 - 127 1 〇 F10.13 Communication Address of DeviceNet Expansion Card 0 - 63 1 〇 No. Function Range Unit Default Type F10.14 Response Delay Time of Process Data of Communication Card 0.0 - 200.0 ms 0.0 〇