sinee — 7.14 F13 Group: Torque Control Parameter

EM500 Open-Loop Vector Control Inverter User Manual The way of digital potentiometer given refers to main frequency source A given. 7.14 F13 Group: Torque Control Parameter F13.00=0: Speed Control The control mode is the speed input type, with the frequency as the input. F13.00=1: Torque Control current; only under SVC control mode, i.e., F00.01=1 can it be enabled. Input control mode is torque input and input is the percentage of motor rated torque The final control mode is also related to “29: Torque Control Disabled” and “28: Switch between Speed Control and Torque Control”. See corresponding description.

Table 7-18 Final Control Mode of Inverter 273 frequency reference F12.43 Digital potentiometer torque reference 0.00~| F13.02| % 0.0 × No. Function Range Unit Default Type F13.00 Speed/Torque Control 0: Speed Control 1: Torque Control 0 〇 Final 29: Torque Control 28: Switch between Speed F13.00 Control Disabled Control and Torque Control Mode Enabled * * Speed Control Disabled Enabled 0 Torque Control 1 Speed Control Disabled 0 Speed Control 1 Torque Control No. Function Range Unit Default Type F13.01 Torque Setting 0: Numeric Torque Setting F13.02 1: AI1 2: AI2 0 〇